Who hasn’t seen them – images of the last flood on the Rhine, Danube, Elbe and Saale?
The result: environmental damage from burst oil tanks and danger from LPG tanks that were washed away! It doesn’t have to turn out this way!

Alternatives:

  • STAG LPG flood tanks for the safe storage of your liquid gas.
  • Robust
  • Sturdy grille to protect against floating debris up to 30kN
  • Cross beam for increased stability
  • Completely submersible
  • Flow velocity of up to 3 m/s in the event of flooding (according to TRAS 310)

General information

  • Max. permissible pressure PS: 15.6 bar
  • Maximum filling: 85 %
  • Volume V: see table
  • Type of gas: butane/propane
  • Min./max. permissible temperature TS: -40/+40

All liquid gas tanks are equipped with:

Fill valve
Liquid discharge valve
Gas discharge valve with
  • Manual outlet valve with sounding pipe
  • Overfill protection
  • Pressure gauge
  • Test connection
Safety valve
Level indicator
Nominal capacity in
litres
A Ø
[mm]
B
[mm]
C
[mm]
D
[mm]
E
[mm]
F
[mm]
G
[mm]
Weight
[kg]
Order no.
RAL 9010 white
Order no.
RAL 6019 green
27001250248013058501400159015065004311-901004311-6019
48501250428030008501400159015095004312-901004312-6019
6400 lateral12505500420085014001590150115004313-901004313-6019
6400 central12505500420085014001590150115004314-901004314-6019

Information regarding the production of concrete slabs for buoyancy controls

Concrete slab

Nominal capacityHIJGradeMin. volume
[l][mm][mm][mm] [m³]
270065024001200C30/371.8
485070042001200C50/603.5
640080048001200C50/604.5
Downloads